Laboratory
Facilities / Secondary Barriers for Biological Safety Level 3
/ Biosafety Level 3 - BSL3
1. The laboratory is separated from areas that are open to unrestricted
traffic flow within the building, and access to the laboratory is
restricted. Passage through a series of two self-closing doors is
the basic requirement for entry into the laboratory from access
corridors. Doors are lockable. A clothes change room may be included
in the passageway.
2. Each laboratory room contains a sink for handwashing. The sink
is hands-free or automatically operated and is located near the
room exit door.
3. The interior surfaces of walls, floors, and ceilings of areas
where BSL-3 agents are handled are constructed for easy cleaning
and decontamination. Seams, if present, must be sealed. Walls, ceilings,
and floors should be smooth, impermeable to liquids and resistant
to the chemicals and disinfectants normally used in the laboratory.
Floors should be monolithic and slip-resistant. Consideration should
be given to the use of coved floor coverings. Penetrations in floors,
walls, and ceiling surfaces are sealed or capable of being sealed
to facilitate decontamination. Openings such as around ducts and
the spaces between doors and frames are capable of being sealed
to facilitate decontamination.
4. Bench tops are impervious to water and are resistant to moderate
heat and the organic solvents, acids, alkalis, and those chemicals
used to decontaminate the work surfaces and equipment.
5. Laboratory furniture is capable of supporting anticipated loading
and uses. Spaces between benches, cabinets, and equipment are accessible
for cleaning. Chairs and other furniture used in laboratory work
should be covered with a non-fabric material that can be easily
decontaminated.
6. All windows in the laboratory are closed and sealed.
7. A method for decontaminating all laboratory wastes is available
in the facility and utilized, preferably within the laboratory (i.e.,
autoclave, chemical disinfection, incineration, or other approved
decontamination method). Consideration should be given to means
of decontaminating equipment. If waste is transported out of the
laboratory, it should be properly sealed and not transported in
public corridors.
8. Biological safety cabinets are required and are located away
from doors, from room supply louvers, and from heavily-traveled
laboratory areas.
9. A ducted exhaust air ventilation system is provided. This system
creates directional airflow which draws air into the laboratory
from "clean" areas and toward "contaminated" areas. The exhaust
air is not recirculated to any other area of the building. Filtration
and other treatments of the exhaust air are not required, but may
be considered based on site requirements, and specific agent manipulations
and use conditions. The outside exhaust must be dispersed away from
occupied areas and air intakes, or the exhaust must be HEPA-filtered.
Laboratory personnel must verify that the direction of the airflow
(into the laboratory) is proper. It is recommended that a visual
monitoring device that indicates and confirms directional inward
airflow be provided at the laboratory entry. Consideration should
be given to installing an HVAC control system to prevent sustained
positive pressurization of the laboratory. Audible alarms should
be considered to notify personnel of HVAC system failure.
10. HEPA-filtered exhaust air from a Class II biological safety
cabinet can be recirculated into the laboratory if the cabinet is
tested and certified at least annually. When exhaust air from Class
II safety cabinets is to be discharged to the outside through the
building exhaust air system, the cabinets must be connected in a
manner that avoids any interference with the air balance of the
cabinets or the building exhaust system (e.g., an air gap between
the cabinet exhaust and the exhaust duct). When Class III biological
safety cabinets are used they should be directly connected to the
exhaust system. If the Class III cabinets are connected to the supply
system, it is done in a manner that prevents positive pressurization
of the cabinets
11. Continuous flow centrifuges or other equipment that may produce
aerosols are contained in devices that exhaust air through HEPA
filters before discharge into the laboratory. These HEPA systems
are tested at least annually. Alternatively, the exhaust from such
equipment may be vented to the outside if it is dispersed away from
occupied areas and air intakes.
12. Vacuum lines are protected with liquid disinfectant traps and
HEPA filters, or their equivalent. Filters must be replaced as needed.
An alternative is to use portable vacuum pumps (also properly protected
with traps and filters).
13. An eyewash station is readily available inside the laboratory.
14. Illumination is adequate for all activities, avoiding reflections
and glare that could impede vision.
15. The Biosafety Level 3 facility design and operational procedures
must be documented. The facility must be tested for verification
that the design and operational parameters have been met prior to
operation. Facilities should be re-verified, at least annually,
against these procedures as modified by operational experience.
16. Additional environmental protection (e.g., personnel showers,
HEPA filtration of exhaust air, containment of other piped services
and the provision of effluent decontamination) should be considered
if recommended by the agent summary statement, as determined by
risk assessment, the site conditions, or other applicable federal,
state, or local regulations.
|